Home / All / Limit Meter / Energy Limiter /
Fully electronic energy meters Energy Limiter for Solar, Wind or Hybrid Power
Fully electronic energy meters Energy Limiter for Solar, Wind or Hybrid Power
Categories | Limit Meter / Energy Limiter |
---|---|
Brand | ZOYEA |
Update Time | Dec 5,2024 |
Detail Information
Introduction
This is a single-phase two-wire electronic active Energy Limiting DC Meter, front board, wall mounting, with build-in Energy Limiter inside. It can set the daily maximum load limit.
Besides Energy Limiting function, other common functions of this Energy Limiting DC Meter (eg: measuring accuracy) completely accord with relevant technical requirements of class 1 single phase active energy meter, stipulated in international standard IEC 62053-21.
This Energy Limiting DC Meter can accurately and directly measure Direct Current (DC) from SOLAR, WIND or HYBRID POWER etc new DC power plants and electricity net.
It can be installed to use indoor.
Application
This Energy Limiting Meter is ideal in SOLAR, WIND or HYBRID POWER etc some new power plants.
It’s suitable for applications where the amount of energy is limited or rationed per day.
It’s useful for tenants, rugged or remote villages, isolated islands.
It also can be equipped for requiring subsidized billing.
General Function
The simplest Energy Limiting DC Meter is a unique new energy meter that limits energy consumed per day to prevent energy over use.
The built-in MCU handles all metering and control function.
This Energy Limiting Meter is equipped with a real time clock and a load relay.
This Energy Limiting Meter also has warning LED indicator to show the status of load relay.
And it is equipped with Overload Current Protection to make it more safer.
Operation Overview
Each Energy Limiting DC Meter can set the starting time (eg: 6:00pm) everyday when the new allocation will begin. As soon as the designated time (6:00pm) is reached, the new allocation will take effect.
Each Energy Limiting DC Meter can set daily limit of energy consumed.
When the daily limit is reached, the meter will automatically cut off the load power, until the next day, a new kWh allocation is provided and take effect when the designated starting time (6:00pm) is reached.
It runs in circle this way.
Features
▲ Daily Energy Limit
▲ Measuring DC energy accurately and directly
▲ Overload Current Protection
▲ Load Relay Warning LED Indicator
▲ 6-digits LED display
▲ Hand Held Unit or Programm in computer setup
▲ Build-in Real Time Clock
▲ Build-in MCU, Standalone Operation
▲ Accuracy Class 1.0
▲ Front Board/Wall Mounting
▲ Wide Rage Current Measurement
▲ Easy Installation & Easy Setup
▲ Light Weight & Good Reliability
Overload Protection
(1). Overload Protection :
Usually the maximum current for the Energy Limiting Meter is 10A only.
When the current reach 20A, the meter will turn off in 30 seconds;
When the current reach 30A, the meter will turn off in 15 seconds;
When the current reach 40A, the meter will turn off in 5 seconds.
If the meter overload, LED is blinking "P_OV".
(2). Restore:
The Energy Limiting Meter will restore after 30 seconds for over-load off. If over-load is still there, it
will perform the over-load protection process.
After 10 attempts, it will stop the restore operation.
At this time, the users have to restore it manually.
Setup Options
Energy Limiting DC Meter can be set/controlled by
★ Hand Held Unit
★ Programm in computer.
Hand Held Unit Function
Hand Held Unit is use for setting the meter parameters, such as Daily Limit, Alarm Energy, Time, Date, Power On ( Relay ) etc. It can connect with Energy Limiting DC Meter directly by RJ11 port.
The basic functions as:
15 keys & 16 x 2 LCD display
No battery required (RJ11 powered)
Build-in real time clock and calendar
Set Starting Time
Set Daily Usage Limited kWh ( Energy )
Set Daily Usage Limited kW ( Active Power )
Set Power on ( Load Relay restore )
Set Daily Maximum Power Limit ( Overload )
Ordering Code
Rate Voltage ( V )
|
Rate Current ( Ib/Imax ) A
|
Operating Current Range(A)
|
|
METER | 12 ~ 48 | 5 ( 40 ) A | 0.05% Ib ~ Imax |
HHU | RJ11 Power | PLC DC-Com | Data A+, B- ( 2-wire ) |
Technical Specification
Connecting Mode
|
Direct Connections
|
Accuracy Class
|
Class 1.0
|
Operating Voltage | 12 ~ 36 V DC / 36 ~ 48 V DC |
Rated Current (Ib) | 5 A direct connection |
Maximum Current (Imax) | 5A & 40A direct connection |
Operating Current Range | 0.5%Ib ~ Imax |
Internal Power Consumption | <3W |
Operating Humidity Range | <95% |
Storage Humidity Range | <75% |
Operating Temperature Range | -20℃ ~ + 55℃ |
Storage Temperature Range |
-30℃ ~ + 65℃ |
Pulse Output rate (meter constant) | 10000 imp/kWh ( for 5A ), 8000imp/kWh ( for 40A ) |
Display | 6-Digits Register, LCD Display (L) |
Overall Dimensions (W x H x D) | W: 162 mm x H: 116 mm x D: 66 mm |
Overall Dimension Installation
Application
Related Products
Please send your message to us
- Tel
- *Title
- *Content
newsletter
Subscribe to the Molotok mailing list to receive updates on new arrivals, special offers and other discount information.
subscription